Re: [TRNSYS-users] Questions on VENTILAT [KWH]



I believe that the definition of the ventilation gains in Type56 (whether in the standard output file or from NTYPE 5 is equation 6.4.1-3 in the volume 06-MultizoneBuilding documentation:

qVent = Vdot_vent * Cp_air * rho_air * (Tventilation - Troom)

Regards,
 David


#TEO NGUAN TECK# wrote:

Hi ALL,

 

In T56_std-Output file, there is a column that summarized the values for VENTILAT in KWH.

 

Does a positive value imply that my external ventilation system is adding heat to my zones?

How does TRNSYS determine the value?

 

Any help is appreciated.

 

Nguan Teck

NTU Singapore


_______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users

-- 
***********************************************************************