Chun Kwong,
 I think you might want to look back at your window data - as you can see from the warnings leading up to the one that you highlighted, Type56 is not able to converge on a window pane temperature (it has calculated the pane temperature as "non a number" (NaN).) One thing you might try to do is to turn off any automatic heat transfer coefficient calculations on your windows. Usually, it is not a problem but for certain windows that have window pane temperatures that are sensitive, that heat transfer coefficient can change dramatically from one iteration to the next and cause problems converging on a pane temperature.
Kind regards,
 david