Dear COMIS users, An increasing number of users contact me about numerical
problems running coupled simulations (using COMIS as a TYPE in TRNSYS). It appears that a good deal of these problems is
simply due to an unfortunate default value used in the graphical environment of
COMIS: the default solver used for COMIS by Simulation Studio is solver 1 ( For coupled projects, however, solver 6 (trust region
line search) is more appropriate. So if you encounter problems running coupled
projects, you should just try to -
change the solver in the
COMIS (*.cpf) project (Assembly/Control cards/Control tab, select “ -
re-write the COMIS input
file (.cif) from the COMIS project (Calculate/Create Input file) -
Re-run the TRNSYS (.tpf)
project Werner Keilholz Centre Scientifique et
Technique du Bâtiment Évitez d’imprimer vos
emails inutilement. Respectez l’environnement Ce message et toutes les pièces
jointes sont confidentiels et exclusifs pour le destinataire du message.
N'importe quelle autre distribution, utilisation ou reproduction est non
autorisée et interdite. Si vous receviez ce message par erreur, informez svp
l'expéditeur immédiatement et supprimez le message de votre système. ************************************************************************************ This footnote confirms that this email message has been scanned by PineApp Mail-SeCure for the presence of malicious code, vandals & computer viruses. ************************************************************************************ |