Ordoumpozanis Konstantinos, If the simulation begins to have problems at very high flow rates, check to make sure that there is actually enough pipe volume in your system to contain the amount of fluid that you are trying to pump. You will probably have to decrease the time step, increase the size of the bore field, perhaps add or increase the size of the pipes that lead from the heat pump to the field, and perhaps increase the size of the heat pump itself as well. Kind regards, David Ordoumpozanis Konstantinos wrote:
-- *********************************************************************** Thermal Energy System Specialists (TESS), LLC David BRADLEY 2916 Marketplace Drive - Suite 104 Partner Madison, WI 53719 USA P: +1.608.274.2577 F: +1.608.278.1475 E-mail: bradley@tess-inc.com Web Pages: http://www.tess-inc.com and http://www.trnsys.com *********************************************************************** |