Hello Laura,

I have looked at your project, and see that you have connected the air flow
rate (in kg/hr) from the heat pump directly to the building. The air change
input to the building zones must be in (kg/hr air from heat pump)/(kg air
in zone), so that the unit is 1/h. Put an equation between the heat pump
and the building to do this. Although I have not tried to do these changes
to your project, I think that this must be the error.

Kind regards,
Knut Erik



                                                                       
             trnsys-users-requ                                         
             est@cae.wisc.edu                                          
                                                                        To
             27.08.2008 19:37          trnsys-users@cae.wisc.edu       
                                                                        cc
                                                                       
             Please respond to                                     Subject
             trnsys-users@cae.         TRNSYS-users Digest, Vol 44, Issue
                 wisc.edu              22                              
                                                                       
                                                                       
                                                                       
                                                                       
                                                                       
                                                                       




----- Message from "latara\@libero\.it" <latara@libero.it> on Wed, 27 Aug
2008 19:18:03 +0200 -----
                                                                       
       To: "trnsys-users\@cae\.wisc\.edu" <trnsys-users@cae.wisc.edu>  
                                                                       
  Subject: [TRNSYS-users] problem with building-equipment              
                                                                       

Hello,my name is Laura. I have a problem with my thesis.I don't understand
because I get strange results in my simulation.The internal temperature in
building must be 24-26°C, but I get 8-10°C with heat pump. Why? Where is
the error? I send you my file, please help me.
Thank you in advance.
(See attached file: edificioconimpiantodefinitivoestivo.TPF)(See attached
file: Wizard6conimpianto.bui)(See attached file: IT-Brindisi-163200.tm2)
_______________________________________________






----------------------------------------------------------------------------------------------------------------------
NIVAs hovedkontor har flyttet til nye lokaler i CIENS - Forskningssenter
for miljø og samfunn; Gaustadalléen 21, 0349 Oslo. Meld deg på vårt
nyhetsbrev på www.niva.no

Attachment: edificioconimpiantodefinitivoestivo.TPF
Description: Binary data

Attachment: Wizard6conimpianto.bui
Description: Binary data

Attachment: IT-Brindisi-163200.tm2
Description: Binary data