You need to use an equation and a few Type 14 forcing functions.
Unit 1 Type 14 Forcing Function for Seasonal Switchover
Parameters 12
0,1 2160,1 2160,0 6552,0 6552,1 8760,1
Unit 2 Type 14 Forcing Function for Winter Daily Operation
Parameters 12
0,0 7,0 7,200 18,200 18,0 24,0
Unit 3 Type 14 Forcing Function for Summer Daily Operation
Parameters 12
0,200 7,200 7,1000 18,1000 18,200 24,200
Equations 1
Ventilation=[1,1]*[2,1]+(1-[1,1])*[3,1]