[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]
Re: [TRNSYS-users] Type 56 - strange window U-value
Gilles,
If I understand correctly, Type56 calculates the window U-value at
each time step and at each iteration in the simulation. The u-value at
any point in time is dependent upon a complex calculation of window pane
temperatures, gas cavity temperatures, zone temperature, and ambient
temperature. The u-value reported in the WindowLib is at some reference
condition and is for the center of glass. There is a Type56 output (NTYPE
50 among the "surface outputs") available to show what value
Type56 is calculating for the window u-value during the simulation.
Cheers,
David
At 07:55 10/12/2006, Gilles Fraisse wrote:
dear trnsys users ,
using TYPE 56, we have some problems with the U value of the window. For
exemple, I use this window from the german library (window type, library
...) :
Unit System : SI, Name : TRNSYS 15 WINDOW LIB, Desc :
Waermeschutzglas,Ar, 1.3 71/59, Window ID : 2002, Tilt : 90.0
Glazings : 2, Frame : 11 2.270, Spacer : 1 Class1 2.330 -0.010 0.138,
Total Height: 1219.2 mm, Total Width : 914.4 mm
Glass Height: 1079.5 mm, Glass Width : 774.7 mm
In the *.bui file , I consider an area of 4.15m² . But which value of U
(and of area) is really used in the simulation ? I have compared with the
steady state modelling (constant external temperature - solar radiation
=0, constant internal heat gain ... ) and I cannot find 1.3 W/m²K , nor
0.85*1.3 + 0.15*8.17/3.6 (If I consider the frame). And there's no
problem if I delete the window.
Has anybody carried-out the same steady state checking with one
window ?
best regards
G. Fraisse
°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
LOCIE - groupe DENED (Développement Énergétique Durable)
Polytech'Savoie - Université de Savoie
Campus Scientifique Savoie Technolac
73376 - Le Bourget du Lac Cedex (France)
Tel. +33 (0)4.79.75.88.95 (Fax : 81.44)
°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°°
_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users
****************************************************************************************
Thermal Energy System Specialists (TESS), LLC
David
BRADLEY
2916 Marketplace Drive - Suite 104
Partner
Madison, WI 53719
Phone: (608) 274-2577 USA
Fax: (608) 278-1475
E-mail: bradley@tess-inc.com
Web Pages:
http://www.tess-inc.com
and
http://www.trnsys.com
"Providing software solutions for today's energy engineering
projects"
****************************************************************************************