[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

AW: [TRNSYS-users] how to get the general U-value?



Title: Nachricht
The value after "End of library" is a display only value for TRNBUILD. Type 56 does the u-value calculation internally depending on temperatures and so on.
The displayed values are only for certain boundary conditions valid.  Unfortunately the conditions of the doe2 output are not the same as of  EN410-Norm. 
But those conditions can be changed in W5 at Libraries\Environmental Conditions\..
Trnbuild now takes from the w4-lib data the red marked condition. We changed that in the new TRNBUILD-Version  to the green marked value because this value is closer to the
EN410 condition.
 
Overall and Center of Glass Ig U-values (W/m2-C)
Outdoor Temperature                 -17.8 C      15.6 C      26.7 C      37.8 C
Solar      WdSpd  hcout hrout  hin
(W/m2)     (m/s)     (W/m2-C)
   0        0.00  12.25  3.24  7.59  1.44 1.44  1.35 1.35  1.38 1.38  1.45 1.45
   0        6.71  25.47  3.21  7.62  1.51 1.51  1.39 1.39  1.43 1.43  1.51 1.51
 783        0.00  12.25  3.41  6.82  1.41 1.41  1.42 1.42  1.47 1.47  1.53 1.53
 783        6.71  25.47  3.31  7.10  1.51 1.51  1.45 1.45  1.51 1.51  1.56 1.56

 
*** END OF LIBRARY ***
********************************************************************************
*WinID  Description   Aufbau   U-Value  g-value  T-sol   Rf-sol   T-vis  
********************************************************************************
5001 Double,low-e,Ar  3.0/12.7/2.5             1.5    0.596    0.544    0.220   0.769

 
Krypton has a very low conductivity but a high ratio of the convection with in the gap which is depending on the temperature difference between inner and outer pane.
So the u-value changes more with a the temperature difference.
There for a difference in the boundary conditions to the norm conditions has a greater influence for Krypton.
The best of course  would be to have DOE2 Output with EN410 conditions for g and u value.
 
best regards

Torsten Welfonder

--------------------------------------------------------------------------------------------------------------------
*  TRANSSOLAR Energietechnik GmbH   
*  Curiestrasse 2
*  70563 Stuttgart
*  Germany
*
*  Tel: 49 (0)711 67976-0                     
*  FAX: 49 (0)711 67976-11
*
Mailto:Hotline@transsolar.com                                                                 
http://www.transsolar.com                                                             
http://www.trnsys.de                                                          
--------------------------------------------------------------------------------------------------------------------
TRNSYS-Usertag 2005
When?           18.03.2005;  9.00 - 18.00 Uhr
Where?          Stuttgart
Language?       German and english
price?          150,- per person before 31.12.2004
                210,- per person after 31.12.2004 + VAT

TRNSYS-courses 2005
course 1:               Introduction into the work with TRNSYS
Price: 990,- per person, + VAT 
2./3.06.2005
course 2:               Building Simulations with TRNSYS
Price: 990,- per person, + VAT
15./16.06.2005
course 4:               airflow simulation in buildings TRNFLOW 
Price: 690,- per person, + VAT
17.06.2005
--------------------------------------------------------------------------------------------------------------------
TRNSYSlite 3.0  more information about TRNSYSlite30 can be found at: http://www.trnsys.de/ts/english/softeng/tliteeng/tliteeng.htm.

--------------------------------------------------------------------------------------------------------------------
New: TRNSYS16           more information about TRNSYS16 can be found at: http://www.trnsys.de/ts/english/softeng/trneng/trneng.htm.

--------------------------------------------------------------------------------------------------------------------
TRNFLOW         more information about TRNFlow can be found at: http://www.trnsys.de/ts/english/softeng/floweng/floweng.htm.

--------------------------------------------------------------------------------------------------------------------
if you need any further information please contact hotline@transsolar.com.



 
 
-----Ursprüngliche Nachricht-----
Von: trnsys-users-bounces@engr.wisc.edu [mailto:trnsys-users-bounces@engr.wisc.edu] Im Auftrag von Isabelle BRUYERE
Gesendet: 17 February 2005 09:42
An: Pietro Filippi; trnsys-users@engr.wisc.edu
Betreff: Re: [TRNSYS-users] how to get the general U-value?

Hi Pietro,

Sorry I can't help you with that one. But I also noticed some difference between the U value given by WINDOW5 and the one showed by TrnBuilt, especially when you use Krypton between the glasses.
Does anybody have an explanation for that ?

Best regards,

Isabelle


A 17:55 16/02/2005 +0100, Pietro Filippi a écrit :
Content-class: urn:content-classes:message
Content-Type: multipart/alternative;
        boundary="----_=_NextPart_001_01C51448.61342D9C"

sorry for another question,
I "decoded" the reported data from Window 5 as edited in W4-lib.dat file in order to describe the global value as described at the "END OF THE LIBRARY" in this file (see the example below). I found an exact corresspondence for all the data except for the U-value, whose reported value I suppose to be a mean value of the reported ones in the "Overall and Center of Glass Ig U-values (W/m2-C)" lines. but which ones?
Otherwise I thought it should simply be the global value reported for the glazing system of a given window, but I cannot verify it since a can't resume the Trnsys W4-lib story of course...
can anybody confirm to me that it is correct to assume for U-value what given for the glazing system and not get it from the Window 5 report?
thanks in advance
Pietro
 
 
WINDOW 4.1  TRNSYS 14.2 Data File : Multi Band Calculation
 
Unit System : SI
Name        : TRNSYS 14.2 WINDOW LIB
Desc        : Dble,Low-e,Ar
Window ID   : 5001  
Tilt        : 90.0
Glazings    : 2
Frame       :  1 Al no break          10.790
Spacer      :  1 Class1                2.330  -0.010   0.138
Total Height: 1219.2 mm
Total Width :  914.4 mm
Glass Height: 1104.9 mm
Glass Width :  800.1 mm
Mullion     : None
Gap        Thick   Cond  dCond    Vis   dVis   Dens   dDens     Pr     dPr
1 Argon     12.7 0.01620  5.000  2.110  6.300  1.780 -0.0060  0.680 0.00066
2              0       0      0      0      0      0       0      0       0
3              0       0      0      0      0      0       0      0       0
4              0       0      0      0      0      0       0      0       0
5              0       0      0      0      0      0       0      0       0
Angle     0    10    20    30    40    50    60    70    80    90 Hemis
Tsol  0.544 0.548 0.539 0.529 0.514 0.486 0.426 0.312 0.145 0.000 0.453
Abs1  0.187 0.190 0.200 0.207 0.210 0.218 0.242 0.273 0.248 0.001 0.221
Abs2  0.048 0.049 0.049 0.050 0.051 0.052 0.050 0.045 0.033 0.000 0.048
Abs3      0     0     0     0     0     0     0     0     0     0     0
Abs4      0     0     0     0     0     0     0     0     0     0     0
Abs5      0     0     0     0     0     0     0     0     0     0     0
Abs6      0     0     0     0     0     0     0     0     0     0     0
Rfsol 0.220 0.214 0.212 0.214 0.224 0.244 0.282 0.371 0.574 0.999 0.268
Rbsol 0.236 0.231 0.230 0.232 0.241 0.261 0.307 0.414 0.629 1.000 0.291
Tvis  0.769 0.774 0.763 0.749 0.730 0.692 0.605 0.440 0.205 0.000 0.642
Rfvis 0.138 0.131 0.128 0.131 0.143 0.168 0.217 0.323 0.549 0.999 0.197
Rbvis 0.127 0.120 0.119 0.124 0.138 0.168 0.233 0.379 0.650 1.000 0.208
SHGC  0.596 0.600 0.592 0.583 0.569 0.543 0.483 0.366 0.188 0.000 0.507
SC: 0.69

 
 
 
Layer ID#          400        1        0        0        0        0
Tir              0.000    0.000        0        0        0        0
Emis F           0.840    0.840        0        0        0        0
Emis B           0.100    0.840        0        0        0        0
Thickness(mm)      3.0      2.5        0        0        0        0
Cond(W/m2-C     )300.0    360.0        0        0        0        0   
Spectral File     None     None     None     None     None     None

 
Overall and Center of Glass Ig U-values (W/m2-C)
Outdoor Temperature                 -17.8 C      15.6 C      26.7 C      37.8 C
Solar      WdSpd  hcout hrout  hin
(W/m2)     (m/s)     (W/m2-C)
   0        0.00  12.25  3.24  7.59  1.44 1.44  1.35 1.35  1.38 1.38  1.45 1.45
   0        6.71  25.47  3.21  7.62  1.51 1.51  1.39 1.39  1.43 1.43  1.51 1.51
 783        0.00  12.25  3.41  6.82  1.41 1.41  1.42 1.42  1.47 1.47  1.53 1.53
 783        6.71  25.47  3.31  7.10  1.51 1.51  1.45 1.45  1.51 1.51  1.56 1.56

 
*** END OF LIBRARY ***
********************************************************************************
*WinID  Description   Aufbau   U-Value  g-value  T-sol   Rf-sol   T-vis  
********************************************************************************
1001 Single_Pane            4                   5.8    0.870    0.850    0.075   0.901
2001 Double_Pane      2.5/12.7/2.5              2.7    0.777    0.727    0.129   0.817
3001 Triple_Pane      2.5/12.7/2.5/12.7/2.5     1.8    0.700    0.624    0.168   0.744
4001 Double,low-e     3.0/12.7/2.5              1.7    0.597    0.544    0.220   0.769
5001 Double,low-e,Ar  3.0/12.7/2.5             1.5    0.596    0.544    0.220   0.769

 
 
 
 
Ing. Pietro Filippi
Nier Ingegneria SpA
www.niering.it
Via Altabella 3, 40126 Bologna
tel: +39 051234359
fax: +39 051239530
 
_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users

Isabelle Bruyère                                                
Université Catholique de Louvain                        Place du Levant, 1 à 1348 Louvain-la-Neuve
Unité d'architecture - Architecture et Climat           Tél : 010/47 21 38 - Fax : 010/47 21 50

http://www-climat.arch.ucl.ac.be/