[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] trnsys type 56 request



Hye Ahmed,
 
Last month, I have study the possibilities to change the emissivity of the internal walls in TYPE 56. But, TYPE 56 fixes the emissivity to 1 for the internal walls and the view factor is equal to the ratio of the emitted areas.
 
You can tuned the surface emissivity of the internal walls by changing the Tmean value in PreBid in order to compensate the effect of a change of emissivity. This change has an effect on all heat transfers by radiation.
 
In attachment, you will find a repport (project IEA34/43) which gives you more details.
 
Bye.
----- Original Message -----
Sent: Friday, November 26, 2004 4:02 PM
Subject: [TRNSYS-users] trnsys type 56 request

Hi trnsys users,

I want to know if with type 56 we can change the emissivity of the internal surfaces of a building.

 

Thanks

 

Ahmed

 

Attachment: MZ - Spec - 0514041.doc
Description: MS-Word document

Attachment: MZ - Repport - ULg ChA 20041116.doc
Description: MS-Word document