[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] invalid floating point operation



Vincent CORNILLON wrote:

Dear Trnsys users.
I have a simple simulation with a type 9f (french weather), a type 16i, a
type 56 (multizone building created with Prebid) and a type 65.

My simulation always at time step 21 with this two messages:

"range check error"
"invalid floating point operation"

Do you know what is the problem and how can avoid it?

thank you for your help

Vincent Cornillon


_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users

Dear Vincent,

the most propable reason for this error is a problem in the connections.
A common error is to forget to hook the 'Time of last read" and "Time of
next read" of type 9 to the respective inputs of type 16.

If this is not a problem, feel free to send us your project to look at.

Werner

--


 /    \____ Werner Keilholz, Software Development Group Leader
 \____/     CSTB Sophia Antipolis, SAIL
 /    \____ s-mail: BP 209, 06904 SOPHIA ANTIPOLIS,  F R A N C E
 \____/     phone: +33 (0)4 93 95 67 00 -- fax: +33 (0)4 93 95 67 33
 /    \____ Mailto:werner@cstb.fr -- ASPAM=antispamwpk42
 \____/     http://evl.cstb.fr/english/team/WK/werner.htm

WARNING : Email is not a reliable medium. Never asume that any email you send is actual read by a human being.